| Itemsl |
Specifications and standards |
| DC Input |
35V〜60V 40V〜70V or 35V〜70V |
| AC Output |
Single phase 115V/120V/200V/220V 50/60Hz
(possible to output by single phase three wires)
|
| Efficiency |
93%(90%Min,in DC input 35V〜60V) |
| Power factor |
0.7〜1.0Max.in 20%〜100% load |
| Input side ripple rate |
3% Max. |
| Display |
Input voltage,current and electric power voltage,
current and conversion efficiency
|
| Coordination |
Commercial power supply system coordination
current control (numerical display)
|
| Dimensions |
H165×W360×D233m/m (installation type) |
| Weight |
9.5kg |
| Rating |
Continuous |
| Cooling system |
Compulsory cooling |
| Main ciruit method |
Voltage type of current control PWM inverter |
| Isolation system |
High frequency isolation |
| Electric power control system |
By direct current voltage from the outside |
| Output control system |
Current control system |
| Subsidiary control |
Soft start |
| Operation control |
Automatic start
Start/stop by watch of,direct current voltage
Start condition:35V DC Min,for 1 min,for 1 min
successively or 40V DC min,for 1sec, successively |
DC
input |
Rated voltage |
48V DC |
| Rated current |
30A DC (0〜50A but the output is up to 1.3kw Max |
Input fluctuation
voltage |
35V〜70V DC |
| Current ripple rate |
5% Max.( peak to peak ) |
System
corditions |
Phase |
Single phase three wires |
| Voltage |
220V |
| Voltage change range |
±13V |
| Frequency |
60Hz |
| Frequency change range |
±0.3% Max. |
Power
generation
output |
coordinative
operation |
Output capacity |
1300W Max. |
| Conversion efficiency |
90% Min |
| Output power factor |
0.95 Min |
| Harmonics current |
Total current distortion factor 5% Max.
Each current distortion factor 3% Max. |
Independent
operation |
Rating Load capacity |
1000VA |
| Rated voltage |
220V |
| Constant voltage accuracy |
±3% Max |
| Waveform distortion |
3% Max. |
Endurance amount of
fault load |
110% (100%=4.54A) |
| Transient voltage fluctuation |
±7% Max. |
| Frequency accuracy |
±0.1Hz Max. |
Coordinated
protection |
Coordinated protection relay |
Alternating,current,fault voltage protection,
alternating current instant fault voltage,
Frequency rise detection,Frequency decline
detection,alternating current voltage decline
detection,instant voltage decline detection
|
| Independent operation |
Passive system |
Voltage phase jump
detection system |
|
Active system |
Frequency shift system |
| Insulation resistance |
The 1st order-the 2nd order,electric current in block-outside box 10MΩ
Min |
| Dielectric strength |
Electric current ,in block-outside box 1500V AC
for 1 minute
|
| Noise |
45db Max.(1m) |